These valves blend hot and cold supply water to deliver tepid water (85°F / 29°C) to emergency equipment, and with a range of 2 to 7 GPM at 30 PSI (7.5 to 26.5 LPM at 2 BAR G), this low-capacity valve is sufficient for a single eyewash. Best specified for systems requiring bypass rates of 1 to 7 GPM (3.7 to 26.5 LPM). The valve can be installed into existing emergency eyewash application and is easily tested and repaired. Helps meet ANSI Z358.1-2014 and accurately controls outlet temperature in accordance with ASSE 1071 standards. ASSE 1071 approved and lead free certified.
Product Summary:
- Patented thermostatic element provides comfortable water regardless of changes in incoming hot/cold water temperatures
- Positive hot water shut-off eliminates the delivery of scalding water to equipment
- Integral cold water bypass ensures reliable cold water delivery if hot water supply is interrupted
Specifications
Model No | TMVEF |
---|---|
UPC | 805042000755 |
Net Weight, lbs | 4 |
Net Weight, kg | 3 |
Dimensions, Exterior | 8" H x 9" W x 5" D |
203mm H x 229mm W x 229mm D | |
Water Inlet Size NPT | 1/2 in (F) |
Minimum Operating Pressure | 2.4 bar g, 35 PSI |
Maximum Operating Pressure | 8.6 bar g, 125 PSI |
Material Specifications | Bronze Body |
Documentation:
Product Datasheet TMVEF (834.48 KB)