These valves blend hot and cold supply water to deliver tepid water (85°F / 29°C) to emergency equipment, and with a range of 2 to 60 GPM at 30 PSI (7.5 to 227 LPM at 2 BAR G), this high-capacity valve is sufficient for multiple emergency showers and/or eyewash stations installed in the same supply line. Best specified for systems requiring bypass rates of 14 to 45 GPM (53 to 170 LPM). The valve can be installed into existing emergency shower applications and is easily tested and repaired. Helps meet ANSI Z358.1-2014 and accurately controls outlet temperature in accordance with ASSE 1071 standards. ASSE 1071 approved and lead free certified.
Product Summary:
- Redundant thermostatic elements provide tepid water in the event of a thermostatic failure
- Positive hot water shut-off eliminates the delivery of scalding water to equipment
- Integral cold water bypass ensures reliable cold water delivery if hot water supply is interrupted
Specifications
Model No | TMVM |
---|---|
UPC | 805042000731 |
Net Weight, lbs | 26 |
Net Weight, kg | 12 |
Dimensions, Exterior | 8" H x 11" W x 5" D |
203mm H x 280mm W x 280mm D | |
Water Inlet Size NPT | 1-1/4 in (F) |
Minimum Operating Pressure | 2.4 bar g, 35 PSI |
Maximum Operating Pressure | 8.6 bar g, 125 PSI |
Documentation:
Product Datasheet TMVM (882.45 KB)